| RLS |
Model |
28 |
38 |
50 |
| Capacity (MBTUH)(1) |
378 - 1,232 |
434 - 1,666 |
546 - 2,198 |
| Capacity (GPH)(2) |
2.7 - 8.8 |
3.1 - 11.9 |
3.9 - 15.7 |
Combustion Air Motor |
Voltage(3)(4) |
120/1/60 |
120/1/60 |
230 - 460 - 575/3/60 |
| HP |
1/2 |
1/2 |
3/4 |
| Amperage Draw |
5.2 |
5.2 |
3.2/1.6/1.3 |
| Sound Levels |
dBA |
68.0 |
70.0 |
72.0 |
| Max. Chamber Pressure ("w.c) @ high fire |
0.8 |
1.1 |
0.0 |
| Min. Gas Pressure ("w.c)(5)(6) |
6.0 |
7.0 |
6.0 |
(1) Ratings based on 1,000 Btu/ft.3 and .64 specific gravity. (2) Ratings based on 140,000 Btu/gallon for No.2 fuel oil. (3) Other
voltages available on request. (4) A seperate 120/1/60 control voltage supply is required. (5) Based on natural gas. (6) Honeywell, Dungs and Siemens gas trains available. |
|